CWL carbon dioxide sensors maximize energy savings, while ensuring optimal ventilation. The sensors allow ventilation systems to be controlled by the amount of CO2 present in a space. The CWL Series detect fluctuations in CO2 levels and signal ventilation systems to provide an inlet of fresh air optimal for the space at a given time saving energy and ensuring tenant comfort.APPLICATIONS
Controlling ventilation in response to occupancy
Facilitating compliance with ASHRAE 62.1-2004 standard for air quality
Office buildings, conference rooms, schools, retail stores, etc.
Microprocessor design increases accuracy and reduces installation time
Non-dispersive infrared technology (NDIR) repeatable to ±20 ppm ±1% of measured value
Innovative self-calibration algorithm...easy to maintain
5-year calibration interval (recommended)
Low ambient sensitivity
Field-selectable outputs for operation flexibility
Revolutionary direct duct mounting design
Integrated transducer and probe...eliminates the need to install a separate pick-up tube
Snap-on faceplate...no screws required, making installation and service a snap
Adjustable duct probe...simplifies installation and airflow monitoring
CO2, humidity, and temperature sensing all in one compact device...fewer units to buy and install
Series Specifications
Input Power 20 to 30VDC/24VAC; 100mA max.
Analog Output 4-20mA, (clipped & capped)/0-5VDC/0-10VDC (selectable)
Operating Temperature Range 0° to 50°C (32° to 122°F)
Housing Material High impact ABS plastic
CO2 Transmitter:
Sensor Type Non-dispersive infrared (NDIR), diffusion sampling
Measurement Range 0-2000/5000 ppm (programmable)
Accuracy ±30 ppm ±2% of measured value*
Repeatability ±20 ppm ±1% of measured value
Response Time <60 seconds for 90% step change
RH Transmitter:
HS Sensor Fully replaceable, digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138
Accuracy ±2% from 10 to 80% RH; NIST traceable multi-point calibration
Stability ±1% @ 20°C (68°F) annually, for two years
Operating Humidity Range 0 to 100% RH
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Coefficient ±0.1% RH/°C above or below 25°C (typical)
Temperature Transmitter:
Sensor Type Solid-state, integrated circuit
Accuracy ±0.5°C (±1°F) typical
Resolution 0.1°C (0.2°F)
Range 10° to 35°C (50° to 95°F)
Relay Contacts:
1 Form C (SPDT) (on models without setpoint slider option) 1A@30VDC, resistive; 30W max.
RTD/Thermistors in wall packages are not compensated for internal heating of product.EMC Conformance: EN 61000-6-3:2001 Class B, EN 61000-6-1:2001, EN 61000-3-2:2000, EN 61000-3-3:2001, EMC Test Methods: CISPR 22:1997 (Amended A1:2000, A2:2002) Class B, IEC 61000-4-2:2002, IEC 61000-4-3:2006, IEC 61000-4-4:2004, IEC 61000-4-5:2001, IEC 61000-4-6:2004, IEC 61000-4-8:2001, IEC 61000-4-11:2004.EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements).*Measured at NTP